PVC Pipe Schedule to Dimensions and Pressure Converter

Convert PVC pipe nominal size and schedule to outer diameter, inner diameter, wall thickness, and max pressure rating.
Covers Schedule 40 and 80.

Select PVC pipe size and schedule to see all dimensions and pressure ratings.

PVC Pipe Specifications

PVC pipe is sized by nominal pipe size (NPS), which does not correspond to any actual physical dimension of the pipe. The “schedule” number defines the wall thickness and pressure rating. Higher schedule numbers mean thicker walls and higher pressure capacity.

Understanding nominal pipe size: When you buy a “1-inch PVC pipe,” neither the inner diameter nor the outer diameter is actually 1 inch. The outer diameter of all schedule pipes of the same nominal size is identical. What changes between schedules is the wall thickness, and therefore the inner diameter. For example, 1-inch PVC pipe always has an OD of 1.315 inches, regardless of whether it is Schedule 40 or Schedule 80.

Schedule 40 vs Schedule 80:

Schedule 40 is the standard for most residential and light commercial plumbing, drainage, and irrigation. It has a lighter wall thickness and is less expensive. The white (or sometimes gray) color of Schedule 40 PVC is the most familiar type. Maximum working pressures range from about 600 PSI for 1/2-inch pipe down to about 220 PSI for 4-inch pipe (ASTM D1785 ratings, water at 73F). Pressure ratings decrease as pipe diameter increases because the wall gets proportionally thinner relative to the diameter, so hoop stress rises even at the same pressure.

Schedule 80 has a thicker wall, providing higher pressure ratings and greater impact resistance. It is gray or dark gray in color. Schedule 80 is used where pipes are exposed to physical damage, in chemical processing, or where higher pressures are needed. Maximum working pressures range from about 850 PSI for 1/2-inch pipe down to about 320 PSI for 4-inch pipe.

The thicker wall costs you flow, and on small pipe it costs more than people expect. Because the outer diameter is fixed, every extra thousandth of wall comes straight out of the bore, and the bore is what carries water. In half-inch pipe the Schedule 80 cross-section is roughly 23 percent smaller than Schedule 40. By four inches the penalty is down to about 10 percent, because the same wall increase is a much smaller share of a wide pipe. So on a long half-inch run, going up a schedule for the impact resistance can quietly cost you real pressure at the far end, and stepping up a nominal size is often the better answer.

Key dimension relationships:

  • Outer Diameter (OD) is the same for all schedules of a given nominal size
  • Wall Thickness increases with higher schedule numbers
  • Inner Diameter (ID) = OD - (2 x Wall Thickness)
  • Higher schedule = thicker wall = smaller ID = higher pressure rating

Common PVC pipe dimensions:

Nominal OD (in) Sch 40 Wall Sch 40 ID Sch 80 Wall Sch 80 ID
1/2 0.840 0.109 0.622 0.147 0.546
3/4 1.050 0.113 0.824 0.154 0.742
1 1.315 0.133 1.049 0.179 0.957
1-1/4 1.660 0.140 1.380 0.191 1.278
1-1/2 1.900 0.145 1.610 0.200 1.500
2 2.375 0.154 2.067 0.218 1.939
3 3.500 0.216 3.068 0.300 2.900
4 4.500 0.237 4.026 0.337 3.826
6 6.625 0.280 6.065 0.432 5.761
8 8.625 0.322 7.981 0.500 7.625

Working pressure at 73F (ASTM D1785):

Nominal Sch 40 (PSI) Sch 80 (PSI)
1/2 600 850
3/4 480 690
1 450 630
1-1/4 370 520
1-1/2 330 470
2 280 400
3 260 370
4 220 320
6 180 280
8 160 250

Temperature derating: PVC pressure ratings assume a maximum temperature of 73F (23C). As temperature increases, pressure capacity decreases dramatically:

  • At 100F (38C): multiply rated pressure by 0.62
  • At 120F (49C): multiply rated pressure by 0.40
  • At 140F (60C): multiply rated pressure by 0.22
  • PVC should never be used above 140F (60C) as it begins to soften

CPVC for hot water: For hot water applications (up to 200F / 93C), use CPVC (Chlorinated PVC) instead of standard PVC. CPVC pipe has the same sizing system but uses a cream or yellowish color to distinguish it from standard PVC.

Joining methods: PVC pipe is joined using solvent cement (PVC glue) which chemically welds the pipe and fitting together. Always use the correct primer and cement for your pipe type. Schedule 80 fittings can be used with Schedule 40 pipe, but not vice versa (the thinner Schedule 40 fittings may not handle the pressures that Schedule 80 pipe is rated for).


How we build and check this converter

This converter runs entirely in your browser, so the numbers you enter stay on your device. The math behind it is written by hand and tested against worked examples and standard references before the page goes live.

SuperGlobalCalculator is independently built and maintained. See how we build and verify our calculators.

Embed This Calculator

Copy the code below and paste it into your website or blog.
The calculator will work directly on your page.